Detailed Product Description
Network Raised Floor with Slots-506 consists of the same materials as LF505 & the same installation procedure. The only variation is the flank caps and central caps have bend edges on each side. The edges allow for easy placement and secure positioning.
TECHNICAL SPECIFICATION
Linkfloor Network Panel System (NP-LF506) |
Panel Type | Panel Grade | Concentrated Load | Impact Load | Ultimate Load | Uniform Load |
NP LF506 | FS668 | Light | 3.0KN | 560N | 9.0KN | 10KN/M2 |
FS800 | Medium | 3.6KN | 670N | 10.8KN | 12KN/M2 |
FS1000 | Heavy | 4.5KN | 670N | 13.5KN | 20KN/M2 |
Specifications of Computer Room Raised Floor:
Module Set
Module Set size: 600mm×600mm=1 UniPanel + 1 Base Connector + 1 Central Cap + 4 Flank Caps
System height: 40mm-150mm
Main Components of Raised Floor System:
Unipanel
Size: 500mm×500mm
Thickness: 25mm
Top and bottom plate of panel: Steel, corrosion protection with powder coating
Panel body encased with light-weighted cement.
Edges: 4mm recession, 12mm wide at panel borders.
Groove: 7mm wide & 6mm deep to lock caps in place
Pedestals: Galvanized steel, fixed at four corners. Assembled to system's required height
Base connector: Galvanized steel. Used to connect UniPanel's pedestal, and automatically form the standard-distance cable trenches
Central cap: Size: 180mm×180mm
2mm thick steel, corrosion protection by powder coating or electro-deposition. Re-enforced ribs Installed at the intersection of the cable trenches.
Flank cap: Size: 208×136mm
2mm thick steel, corrosion protection by powder coating or electro-deposition. Re-enforced ribs
Caps are aligned to create a grid format and to hide exposed wires